This one surely should "like" simulated sine wave as a source and don't drop to battery?
This one surely should "like" simulated sine wave as a source and don't drop to battery?
But why would it require grid-like sine wave and not go along with whatever is the source, provided source can still be used to charge its batteries? I saw no answers yet, and this "why" is the very key to the discussion.
For example, a common topology in offline UPS is that the inverter and the charger are the same circuit driven differently[0] - so you can't charge the battery while the inverter is carrying load. This is popular at the low-end because you have literally half as much UPS, but makes what you're describing impossible.
Another common issue at the low end is that the inverter isn't thermally sized to run non-stop, they know they can cut a corner because your battery presents a finite and known duty cycle.
There are ways around this, but at some point you end up fixing the wrong problem - eg, it's cheaper, safer, and more resilient to buy a transfer switch instead of uprating two UPS to be capable of daisy-chaining.