Given that there are a lot of existing houses out there, surely drop in replacements should be more prevalent.
What it can't do is both at the same time: make 70°C LWT when it's -28°C outside. It's designed for 65°C LWT (some models 60°C) and can only reach 70°C at a performance penalty (year-round) and can only maintain 70°C LWT down to -15°C and starts to lose max LWT, heating capacity, and even more efficiency below that. (Losing efficiency a few days out of the year is a minor concern. Not being able to meet the heat loss and heat transfer for the building for a few days is a much more serious issue for health and comfort.)
I guess being 2x as efficient (cheap) as electric resistive heating isn't super-terrible, but it's not great either.
Compare this to a favorable groundwater heat pump configuration with good radiators and insulation where the 'outside' (groundwater) is maybe 10°C and the target temp 30°C (close to room temp): (273+10)K/20K = ~14.
To be honest the prices I see out there are still generally 'luxury' anyway. If i am spending £20k on a boiler, then an extra £2k to have a secondary gas system that never/very rarely gets used wouldn't bother me at all.