“The 9-mm long insulated sleeves prevent accidental contact with a bare connector while the plug is partially inserted.”
The CEE 7/7 (E & F hybrid) can not be shorted due to socket design. The Europlug, the British plug, the Italian plug and a few others can not be shorted because the prongs are covered in plastic.
It is actually another problem of the original article: It doesn't show and distinguish between recessed sockets and sockets that are available/allowed to be used in a flat form.
The recess also makes the mechanical mating far more robust and takes away mechanical wear from the prongs. So in contrast to flat designs like the British, where all the force rests on the (admittedly thicker) prongs, Type F avoids that problem by distributing most of the forces into the socket housing. Of course you need to replace that if cracked, but you avoid the danger of cracks in the prongs. Cracked or bent prongs are really a fire danger because if they don't immediately fall of (which is the good case), they might continue to be used, albeit with increased electrical resistance due to the crack. Resistance leads to overheating, overheating leads to fires. And no RCCB/SRCD or OCB will help you there. An AFDD might (if there is an arc, which might be 50% of cases), but nobody has those because they are fairly new, very expensive and only code-required in some special types of buildings (care facilities, hospitals and such).
That is why the Europlug has insulated prongs. It fits where Shuko doesn't.
You actually can not even build a non-recesed Shuko (grounded) socket, because the earth contacts are part of the housing.
Besides, none of what you propose will save someone who builds a male to male cable. Darwin awards have to be awarded.