If you wanted to do this up to code, how would you do it?
If you wanted to do this up to code, how would you do it?
One of the things I think would be most likely to throw up a red flag and immediate fail would be the "suicide plugs".
Even though they're not energized (but rather, used to deliver power to the remote end), most electricians and inspectors wouldn't sit around waiting for you to explain your brilliant power delivery scheme.
The only real way to do this stuff code-compliant would be to purchase and install a real hard-wired UPS system, use properly-installed Romex (or other suitable code-compliant wiring), and get things inspected by the local authorities.
Usually if it's not installed by a licensed electrician, the inspectors will be even more stringent.
Suicide plugs refers to extension cords which have been built (or modified) so they are male/male. One in which the far end will be exposed while energized. In this system, the male plugs will never be energized while exposed.
Mostly because 'sparkies' often wire things up like this and use random extension cords in walls and create fun fire hazards.
I agree that the installation is in 'the spirit of the code', but there are enough little variances that I would take a bet that a random inspector would not pass it on first glance.
Not sure where all this worry of code when selling a house comes from. Code changes. No 20 year old house is up to current code, doesn’t mean you can’t sell it.
Flexible cords and cables shall be used only for the following...(11) Between an existing receptacle outlet and an inlet, where the inlet provides power to an additional single receptacle outlet. The wiring interconnecting [...] shall be a Chapter 3 wiring method. [...]
I don't know what Chapter 3 is though, and in the below study guide link it seems to show a double outlet in the graphic.
https://www.electricallicenserenewal.com/Electrical-Continui...
the code you referenced states 'Between an existing receptacle outlet and an inlet'
the circuit is also unlikely to be arc fault protected, which would mostly likely be required.
also how the romex is run, is not to code.
The situation that is dangerous here is if a power source were to be connected to one of these inlets and it did not have a sufficiently-sized breaker and the other side has a dead short, you are looking at a fire inside your walls.
I just installed a 50 amp generator inlet on my main panel, and even though my generator has a matching 50 amp circuit breaker, I installed a separate matching 2-pole 50a breaker on the inlet circuit. This protects the electrical system from even the most screwed up of generators being connected to the panel.
Here there is a breaker, and if the UPS is disconnected, there is no power. Of course someone could go and plug this into a 30a outlet, however that's something that I wouldn't do, so its not really my issue
> however that's something that I wouldn't do, so its not really my issue
Electrical code is designed so that even an incompetent operator cannot produce a dangerous situation inside a building's electrical system. OSHA, USCSB, et. al. would be the first to tell you that relying on a specific individual to interlock a dangerous situation can result in extremely adverse outcomes.
That would be against code.
There's nothing stopping you from running bare wire through your walls.
There's nothing stopping you from not bothering to ground any outlets.
There's nothing stopping you from using 14AWG romex on a 50 amp breaker.
Etc., Etc.
All of that is against code, and I've personally seen all of that in the wild at people's homes, offices, etc.
If you wanted to do things the #rightway, you'd most likely need a subpanel for the UPS to feed.
If they sell those power inlets which are NEC approved, how can you use them without breaking code? So it MUST be code. But then you ask 10 people and get 10 answers
There are larger UPS's designed for hard-wiring, but they are almost always VERY large. I think that might be the only way to avoid an inlet cord like this
At least in my jurisdiction (America) the only way to achieve what you are trying to achieve is by installing a dedicated subpanel fed by the UPS with appropriate breakers. I believe that such an installation would only be code compliant with a UPS that was designed for such an application (with a hard wired output connection, and appropriately designed disconnects), but a lenient inspector might let you get away with feeding a subpanel from an extension cord as long as as of the breakers and capacity factors work out correctly and the grounding meets code.
The biggest issue I see is that the system is not labeled correctly (at all?). That is a pretty serious issue because if, for example, an emergency worker were to come into the house under the expectation that the power to the house was cut (at the service disconnect) but the house would have live outlets that are otherwise unmarked. See https://www.mikeholt.com/download.php?file=PDF/11_Generators... for more information (the relevant section for your system starts at page 16)
As other commenters have pointed out, just because you can buy something that says NEC approved on the sticker does not mean that it is approved for your application. A good example mentioned elsewhere is using a 16awg SJTW extension cord to power a 15a load--all of the connectors will plug together but the combined solution is obviously not code compliant and even if it doesn't melt/catch fire it will not supply the load with clean power.
So the first question to answer is what NEC allows, but you will then need to double-check for your specific context.
Further, the power inlets are NEC approved but that in no way means that they are approved for this use. I'm far from an expert on the NEC but I can pretty confidently assert that it allows such inlets only for specific uses, and you would need to check carefully that what you propose is one of those uses. A very rough rule of thumb is that you are not normally allowed to have more than one "user-removable plug" on the path to a device. There are a number of exceptions to this, but any time you're plugging into something that plugs into something else, you need to check carefully if what you're doing is allowed.
And as mentioned elsewhere, I doubt the JHA or the manufacturer of the UPS would approve of this kind of installation. There are UPS specifically manufactured for a hardwire installation and that's what ought to be used here. That said, I am sympathetic, because UPS can become very expensive very fast. I'm balking at the cost of 2U rack models from Eaton, he will have had to shell out a good chunk more based on his VA requirements but at least he avoided the significant premium for hardwired.
After the author began the article by whining about the previous owner's outlet wiring, I expected better attention to detail.