In local terms its a fair bit of heating but zooming out it's a drop in the bucket.
According to Google, one ton of water takes about 730kWh to boil. So I think you’re off by an order of magnitude, it’s only ~450 metric tons.
(But this assumes that no heat is radiated away in other forms.)
Otherwise it's 1.16 Wh/kg (or kWh/ton) to rise the temprature by 1°C. Thus one needs a delta of 80°C, so 93 Wh to boil a kg of 20°C water. That's what my napkin math was based on. I used that metric a lot to calculate heat deltas in storage tanks.
My 1500W space heater could boil 4.32 gallons of water every hour. But it isn't.
I'm neither for nor against, but on the physics here: basically all of the energy input as electricity is transformed to heat leaving a datacenter. Only a tiny tiny fraction is emitted as radiation (eg floodlights outside or light in fiber optics) or as kinetic energy (air moving away from fans/vents).
Computers are machines for turning electric energy into heat energy, plus some small useful side effects.
An electronic circuit drawing 1W of input power will dissipate all of that 1W as heat (assuming it's not outputting light or sound or other physical side effects).
Though there might be practical differences though between the excess heat intentionally exhausted, and other heat. Just speaking from a very macro sense.