> What Google is doing is using the huge chillers that would normally be cooling the air in the facility to cool water which is directly pumped into every server.
From the article:
> CDUs exchange heat between coolant liquid and the facility-level water supply.
Also, I know from attaching them at some point that plenty of mainframes used this exact same approach (water to water exchange with facility water), not water to air to water like you describe in this comment and others, so I think you may have just not had experience there? https://www.electronics-cooling.com/2005/08/liquid-cooling-i... contains a diagram in Figure 1 of this exact CDU architecture, which it claims was in use in mainframes dating back to 1965 (!).
I also don't think "This eliminates ANY air based transfer besides the chiller tower." is strictly true; looking at the photo of the sled in the article, there are fans. The TPUs are cooled by the liquid loop but the ancillaries are still air cooled. This is typical for water cooling systems in my experience; while I wouldn't be surprised to be wrong (it sure would be more efficient, I'd think!), I've never seen a water cooling system which successfully works without forced air, because there are just too many ancillary components of varying shapes to successfully design a PCB-waterblock combination which does not also demand forced air cooling.