There's no protection over the bus connections. Any falling conductive item is now a spark hazard.
Using spring loaded alligator clips as test leads apparently for monitoring. I hope that's not a permanent configuration.
Everything is bolted down and I see no inline disconnects or even any fusing except on low voltage sections.
There are exhaust fans but I can't tell if there's inlet fans.
From this one picture, which may not be fair, this is not a safe setup. I would feel uncomfortable with this on my property.
A roof-mounted water tank with a thousand gallons ready to dump into the shed? A drum of baking soda?
Or maybe rebuild the shed out of cinder block and clear any overhanging vegetation?
Maybe this whole setup is on desert dirt with plenty of clearance. The fire plan is "run away and wait."
You could also just bury it so that the worst of the explosion is mostly mitigated. I've also seen small container setup which would probably work better than his (seemingly) wooden shed.
Would be better if the ground was paved around the shed, but it seems to be far enough from other free standing structures.
[0] https://secondlifestorage.com/index.php?threads/glubuxs-powe...
[1] https://secondlifestorage.com/index.php?threads/glubuxs-powe...
The firemen ended up putting the battery, half melted, into a big drum of water and it hook hours to cool off. The concrete was still warm to the touch where it burned for ~30 hours after the situation was sorted out.
The smoke was just absolutely unbelievable. Made me reconsider buying an EV. That fire was no joke.
The MV contactor wasn't even closed, it had 24v powering it for the internal cell balancer from the vendor, that was it.
The extinguisher should be directly inside the door so as not to attract someone to traverse farther into the building without an escape plan.
Of course if he did so then there would be no extinguishers in the picture and then we would also bitch about it.
If he can't reach to grab it because it's too hot, he should have already left.
Dry Powder or CO2 is what you need for energized electrical equipment. And considering there's potential lithium involvement, you might want something more specialized (e.g. F-500 Encapsulator Agent). I agree anything more than a small-scale incident you're just getting the heck out of dodge. I'd have built something along the lines of a concrete bunker, with an automated suppression system to buy time.
If you are outside, it does not tempt you to cross the room. If you are inside, you run for the door, and then turn around and decide if maybe you should just keep running.