I guess there’s some internal resistance or something, but…
I guess there’s some internal resistance or something, but…
The trouble is the wires. A given wire gauge is limited in its ability to conduct current, not power. So if you double to the current, you'll need to have roughly twice as much copper in your walls, in your fuse panel, in your appliance, etc.
Additionally, losses due to heat are proportional to the current. If you double the current and halve the voltage, you'll lose twice as much power by heading the wires. For just a house, this isn't a lot, but it's not zero.
This is why US households still have 240V available. If you have a large appliance that requires a lot of power, like an oven, water heater, dryer, L2 EV charger, etc, you really want to use more voltage and less current. Otherwise the wires start getting ridiculous.
This is not to say that higher voltage is just necessarily better. Most of the EU and the UK in particular has plugs/outlets which are substantially more robust and difficult to accidentally connect the line voltage to a human. Lots of people talk about how much safer, for instance, UK plugs/outlets are than US plugs. If you look at the numbers though, the UK has more total deaths per year to electrocution than the US, despite the fact the US is substantially more populous. This isn't because of the plugs or the outlets, US plugs really are bad and UK plugs really are good. But overall, the US has less deaths because we have lower voltage; it's not as easy to kill someone with 120V as 240V.
So there's a tradeoff. There is no best one size fits all solution.
[1]: https://www.cpsc.gov/s3fs-public/Electrocutions-2011-to-2020...
By modelling the wire as an (ideal) resistor and applying Ohm's law, you can get P = I^2*R. the power lost in the wire is actually proportional to the square of current through it!
Therefore, if you double the current, the heat quadruples instead of doubling! You actually have to use four times the copper (to decrease resistance by 4x and get heat under control), or the wasted energy quadruples too.
Crucially, voltage is not in the equation, so high voltages - tens or hundreds of kilovolts - are used for long distance power transmission to maximise efficiency (and other impedance-related reasons).
Not sure about US, yet some high current lanes (thinks of threephase ~400V x 36A; IEC 60502-1) in the households are actually made of Al, not Cu. They tend to be underground though, the wires in the walls are still Cu.
Cu is more conductive than Al so an Al wire has to have a cross section area about 1.56 times that of a Cu with the same current capacity.
But Cu is also denser than Al so the Al wire is only about 0.47 times the weight of the Cu wire.
Al is is much cheaper than Cu so the Al wire is only about 13% the cost of the Cu wire.
Here is a table of the conductivity (in units of 10^7 S/m), the density, and the cost of copper (Cu), aluminum (Al), silver (Ag), and gold (Au).
Cu Al Ag Au
Conductivity 5.96 3.5 6.3 4.1
g/cm^3 8.96 2.6 10.5 19.3
$/kg 9.03 1.2 1030 92100
If we had a copper wire with a specified capacity in amps, here is what aluminum, silver, and gold wires of the same length and capacity would weigh and cost as a percentage of the weight and cost of the copper wire, and what their diameter would be as a percentage of the diameter of the copper wire. Weight Cost Diameter
Al 49 7 139
Ag 110 12646 97
Au 310 3190000 121Most places with 240V regularly have 16A sockets, allowing a maximum draw of 3840W of power. That’s the limit. Cheap fast kettles will often draw 3000W and boil 250ml of water at room tempature in 30s.
Kettles in the US are often limited to 15A and thus max 1800W (usually 1500W) and take twice as long (60s)
Technology Connections has a great video on this: https://youtu.be/_yMMTVVJI4c
4.18 J/g/C * 250g * (1/ 20,000 kJ/s) * 75C = 3.918sOtherwise, you will very quickly vaporize the water near the heater and the resulting lack of contact will inhibit heating the rest of the water volume.
The US could have toasters and hair dryers that work as well as European ones if everything was wired for 32A, but you only do that for porch heaters or electric vehicle chargers.
240V appliances typically get a 35 or 50A circuit.
But then you also have to deal with the fact that a lot of homes have wiring that can only handle 10A, but someone has replaced the glass fuse with a 20A breaker. Fun stuff.
I suspect some beauty products might also use 20A, or in combination easily reach that.
Going to more than 20amp requires a multiphase circuit which are much more expensive and the plugs are unwieldy and not designed to be plugged and unplugged frequently.
There is no multi-phase power available in the vast majority of US houses. A typical residence has a 120/240 split-phase service, which is single-phase only. A service drop is two hot conductors from two of the three transformer phases and a center-tapped (between the two hot legs) neutral conductor. Either hot leg is 120v to ground and line to line is 240V.
> https://en.m.wikipedia.org/wiki/Split-phase_electric_power
Single-phase breakers are also available in sizes larger than 20A, usually all the way up to 125A.
* Currently using a cable spool which will have problems before blowing the fuse if it's wound up and I draw too much current. It has a thermal cutoff, but I still unspool some extra wire on the floor.