You might be surprised at how well cast iron rads can provide comfort at low outside air temps and low flow temps. (I'm in neighboring Cambridge in an old, poorly/non-insulated house.)
https://news.ycombinator.com/item?id=39144329 has a bit of details on the experiment I ran back in 2022 to prove 135°F flow would work for us. (If you have a condensing boiler, you can run this experiment safely; if you have a non-condensing boiler, you can run it, but not for very long as you'll be damaging the flue and boiler with condensation at these lower temps.)
My outdoor reset curve (sadly, on a gas combi boiler because of the "pretty unusual product" factors) is now set to 105°F at 55°F OAT and 154°F at 0°F OAT (which is lower than the design temperature here, but it gave me more resolution to tweak the line to fit the loss just right; it's spot-on on the lower end, with the system running 22-24 hours per day when it's cold out and stays that way up until around freezing, where the utilization falls off).
Matching the gain to the loss quite closely has resulted in a house that's the most comfortable since we moved in in 2007 and gas bills with the combi went down about 46% (versus a 1990s oil-to-gas conversion of a 1950s boiler, so not a realistic comparison for anything that wasn't built by General Motors [not a typo]).