The article mentions the critical parameters which historically have been sourced from big heavy generators like hydro, coal, nuclear or CCGT plants:
- Frequency regulation: When grid power crashes or surges, the device immediately releases or absorbs energy to minimize fluctuation in the AC frequency;
- Short circuit power: When the grid experiences a short circuit, the crashing voltage releases a tripling or more of current from rotating machines which signals breakers on the grid to activate and quickly isolate the fault;
- Voltage support: Producing current and voltage that are out of phase generates so-called reactive power that pushes the local grid’s voltage up or down to stabilize system voltage and/or increase the flow of real power.
This is about Inertia and frequency control. Not about bulk energy storage.