It used to be the continent used 220V, and the UK used 240V, until we standardized on 230V.
The UK defines this as 230V -6% +10% (i.e. 216.2V – 253.0V), and nominal supply is 240V
The continent defines this as 230V -10% +6% (i.e. 207.0V - 243.8V), and nominal supply is 220 or 230 by region.
We called this harmonisation - in reality it's more like agreeing to disagree. We just fudged the tolerances until everyone was happy.
(To put some context around this - most sites don't receive nominal supply. The actual voltage delivered depends on your distance to the local substation. Typically they over-deliver such that sites closest are a little over, sites furthest are a little under. If they actually delivered ±0%, sites at the edge of their network would be further from nominal. So end-user equipment should be built to expect variation.)
I believe ±10% was the traditional definition, so they just trimmed a little off the top end so it strayed less from Europe's definition - but not enough to actually affect nominal distribution.
Which country are you talking about?