Level 2 connectors are only rated to ~19kw[1] so I imagine that must have had it's own custom connector, and I don't particularly see the 80amp chargers becoming particularly common for home use, newer homes generally only have a 200amp main breaker, so 2 of those would take 100% of your continuous power load [2]. I have a 48amp charger and if I need faster than that I go to one of the local fast chargers and worst case wander around a store for 15/20 minutes.
[1] 80amps at 240v, at least in the US, not sure about the type 2 connector used in EU
[2] code in the US says you should only draw 80% of the rated current if the load is continuous