Trip of multiple generators in Qld and associated load shedding 25-May-21
aemo.com.au
aemo.com.au
Three things that particularly stand out in this regard: the local SCADA for Callide C4 reporting to the operators that the unit was still exporting 278MW when in reality it was motoring, absorbing 50MW, for over half an hour; the generator CB for Callide C4 failing to operate; and the local protection at Calvale substation failing to operate for apparently unknown reasons - all lines into it tripped at the remote ends only.
Note that the operators did not regain control of Callide C4 - after absorbing considerable energy for considerable time, it tore itself apart.