50MW is enough power to supply ~14k homes from different references I've seen.
I'm curious about what normal data centers use for backup power since natural gas and diesel generators don't get much bigger than 2MW. Or maybe they just don't have backup generators.
[1] http://www.datacenterknowledge.com/google-data-center-faq-pa...
[0] https://en.wikipedia.org/wiki/General_Electric_LM6000
[1] http://www.geaviation.com/marine/engines/military/lm6000/
They have gas capable engines (50DF series, 50cm cylinder bore) with ratings up to 975kW/cylinders and up to 18 cylinders or 17MW per genset at 60hz.
They're not the only player in that field. Fairbanks-Morse sells the Colt-Pielstick PC2.6 line with 750kW per cylinder at 600rpm and up to 16 cylinders for 11.5 MW @ 60hz. They also sell MAN 48/60 engines that go up to 21MW and MAN natural gas 51/60 G engines up to 18.5 MW.